TRIMOD HE UPS system by Power Control

Products

Trimod

Legrand TRIMOD HE UPS System

Online double conversion VFI three-phase modular UPS system

Description

Delivering a rated power from 10 to 80kVA, the TRIMOD HE UPS systems are made up of individual single phase modules which are redundant and self-configuring.

The three-phase uninterruptible power supply uses on-line double conversion technology with a modular architecture and the possibility to have N + X redundancy.

Product Features

  • Multi control board function
  • Dual input function
  • Plug & Play technology
  • Menu available in 7 languages
  • Frequency converter fin 40-70Hz fout 50/60Hz (can be selected by the user)
  • Operates with a power-supply unit
  • Three independent output phases
  • Eco Mode
  • EPS Mode
  • Adjustable output voltage with 1V intervals (190÷245V)
  • Bypass activation speed control
  • Events log with date and time
  • Overall historical data and for each individual power module
  • Automatic recognition of the power modules
WARRANTY1 Year Parts (upgradable to 5 Years)
RATING KVA10 - 60
DIMENSIONS (WxDxH)414Wx628Dx1650-1370H (10-30kVA) 416Wx628Dx1370H(40-60kVA)
WEIGHT155-120KG (10-20kVA) 181-146KG (30kVA) 146KG (40kVA) 165KG (60kVA)
INPUT PHASEThree Phase / Single Phase
INPUT VOLTAGE380/400/415 3PH+N+PE (or 220,230,240 1PH)
INPUT VOLTAGE TOLERANCE RANGE400V +15%/-20% - 230V +15%/-20% (10-20kVA) 400V +15%/-20% (30-60kVA)
INPUT FREQUENCY45-65 Hz
OUTPUT OUTPUT PHASEThree Phase / Single Phase
OUTPUT POWER FACTOR1
OUTPUT WAVEFORMSinusoidal
OUTPUT VOLTAGE380/400/415VAC
OUTPUT FREQUENCY50/60 Hz selectable by the user ±2 % (standard), ±14 % (extended)
OUTPUT EFFICIENCYUp to 96%
BATTERY RUNTIMEDependent on battery capacity
BATTERY DC VOLTAGEVRLA - AGM / 240 Vdc
BATTERY CHARGE CAPACITYSmart charge technology. 3-stage advanced cycle
MECHANICAL AC OUTLETSHardwired
OPERATING TEMPERATURE TOLERANCE0 - 40°C
RELATIVE HUMIDITY<95% (non-condensing)
COMMUNICATION2 RS232 serial ports, 1 logical gate, 5 ports with dry contacts, 1 slot for interfaces
OPTIONAL COMMSextended VFC
PARALLELN+X
FUNCTIONSmulti control board, dual input, three independent output phases, ECO mode, EPS mode, Adjustable output voltage with 1V intervals, automatic recognition of power modules