Products

C500R UPS System 6kVA to 10kVA

C500R UPS System

Online double conversion UPS for tower or rack installation

Main applications include small data centres, server rooms, IT facilities, telecoms and networking

Description

Main applications include small data centres, server rooms, IT facilities, telecoms and networking.

When positioned in rackmount form, the C500R has a capacity of 6kVA/5.4kW contained within 3U and 10kVA/9kW contained within 5U, which includes internal batteries to provide standard runtime. Its online double conversion topology completely isolates the output voltage and frequency supplied to the users valuable load from incoming mains power anomalies. In addition, sophisticated ECO functions enable the C500R to achieve an industry leading 97% efficiency.

For a more resilient solution, an additional UPS unit can also be connected in parallel to share the critical load and provide N+1 redundancy.

Product Features

  • Online double conversion topology
  • Intelligent monitoring software
  • Server shut down in the event of a mains fail
  • High efficiency up to 98%
  • 0.9 output power factor
  • Smart LCD display
  • Expandable runtime
  • Parallel capacity for N 1
  • User replaceable, hot swappable batteries
WARRANTY3 Year Parts
RATING KVA6 / 10
DIMENSIONS (WxDxH)438W x 698D x 129H (3U) (C500R-060-B), 438W x 640D x 129H (3U) (C500R-060-C), 438W x 704D x 216H (5U) (C500R-100-B), 438W x 640D x 216H (5U) (C500R-100-C)
WEIGHT46 (C500R-060-B) / 19 (C500R-060-C) 85 (C500R-100-B) / 26 (C500R-100-C)
INPUT PHASESingle Phase
INPUT VOLTAGE220/230/240VAC
INPUT VOLTAGE TOLERANCE RANGE176-276VAC (100% load), 120-276VAC (50% load)
INPUT FREQUENCY50/60Hz
INPUT FREQUENCY TOLERANCE RANGE±10%
OUTPUT OUTPUT PHASESingle Phase
OUTPUT POWER FACTOR0.9
OUTPUT WAVEFORMSinewave
OUTPUT VOLTAGE208/220/230/240VAC
OUTPUT FREQUENCY50/60Hz (±10%)
OUTPUT EFFICIENCY>92% (Line mode - 6kVA), >93% (Line mode - 10kVA), >89% (Battery mode - 6kVA), >90% (Battery mode - 10kVA), >96% (Eco mode - 6kVA), >97% (Eco mode - 10kVA)
BATTERY RUNTIME3 minutes (C500R-060-B), Dependent on battery capacity (C500R-060-C), 5 minutes (C500R-100-B), Dependent on battery capacity (C500R-100-C)
BATTERY DC VOLTAGE180VDC (6kVA), 240VDC (10kVA)
BATTERY CHARGE CAPACITY1A (C500R-060-B) / 8A (C500R-060-C), 1.7A (C500R-100-B) / 8A (C500R-100-C)
MECHANICAL AC OUTLETSIEC C13*2, C19*1 and terminal block (C500R-060-B), IEC C13*2, C19*2 and terminal block (C500R-060-C) IEC C19*4 and terminal block (C500R-100-B), IEC C13*4, C19*2 and terminal block (C500R-100-C)
OPERATING TEMPERATURE TOLERANCE0 - 40°C
STORAGE TEMPERATURE TOLERANCE0 - 40°C
RELATIVE HUMIDITY<95% (non-condensing)
OPERATING ALTITUDE TOLERANCE<1000m
COMMUNICATIONRS232 and USB
OPTIONAL COMMSSNMP / dry contact relays / Modbus
PARALLELUp to 2
FUNCTIONSEPO, Expandable Battery Modules, Rack/Tower Flexibility, Rotatable LCD, Dual Input